Product Overview
Features & Benefits
Horn Igniters
IgnIter CapaCIty
Up to 4 MBtu/hr for ignition and/or support
of main gas, oil or coal burners and up to
15 MBtu/hr with an auxiliary gun.
Depending on burner capacity, the horn
igniter is capable of supporting Class 1 or
2 operations.
Dual Fuel CapabIlIty
The single fuel horn igniter fires either oil or
gas; the dual fuel horn igniter fires either oil
or gas without any change of equipment.
Stable Flame
Combustion air is evenly distributed
throughout the horn for reliable operation;
Forneys design does not include an eddy
plate, thus reducing coke buildup and
overheating.
OptIOnal Flame DeteCtIOn
The flame detector senses flame inside the
horn and discriminates from flames outside
the horn.
relIable IgnItIOn
The High Energy Spark Igniter (HESI) is
fixed at the most efficient light-off position
for repeatable ignition.
e Forney horn igniter is used on tangentially fired boilers for burner
ignition and warm up, typically as a Class 2 igniter. Depending on customer
needs, Forney offers either a single or dual fuel horn igniter. e single fuel
horn igniter fires either oil or gas. e dual fuel horn igniter fires either oil or
gas without a change of equipment, allowing for a quick and effortless change
over of fuel.
Both horn igniter assemblies consist of a mounting plate, an oil or gas gun
for the single fuel horn igniter or a combination oil and gas gun for the dual
fuel horn igniter, a High Energy Spark Igniter (HESI), a combustion air tube,
an optional flame detector, and a horn. e major components are fastened
to the igniter front plate with easily removable connections to simplify main-
tenance. e oil and gas connections utilize stainless steel braided hoses and
optional quick disconnect couplings.
e optional flame detector is mounted on a 1” NPT sight tube, which
provides an unobstructed view of the flame inside the horn. Since the detector
is mounted to the igniter windbox, it does not require cooling air.
On retrofit applications, the existing horn (diffuser) may be reused, if it is
not damaged or deteriorated. As a result, the installation requires only replac-
ing the front plate and internal hardware, minimizing costs.
Forneys horn igniter offers reliable single
or dual fuel ignition and warm-up for
tangentially fired burners and is designed
for maximum flame stability and
detection.
A UTC Fire & Security Company
Forney Corporation • 3405 Wiley Post Road • Carrollton, TX 75006 • 800-356-7740 • Fax 972-458-6650 • www.forneycorp.com
Vedere la pagina 0
1 2

Sommario

Pagina 1 - Horn Igniters

Product OverviewFeatures & BenefitsHorn IgnitersIgnIter CapaCIty Up to 4 MBtu/hr for ignition and/or support of main gas, oil or coal burners

Pagina 2

PACHE / FORNEY 1 / TECH BULLETINS WORKING / SCANS / HORN IGNITERLINE ITEM #11 on Requsition # 42871This is one of the original POSTSCRIPT les submitt

Commenti su questo manuale

Nessun commento